Product Description

0.6/1kV PVC Insulated Power Cable


Application

PVC insulated power cable is suitable for power supply and distribution circuits in manufacturing and processing plant, commercial building or residence at the rated voltage 0.6/1kV or less. The power cables can be flame retardant when used as type ZR.

Installation Temperature:

The installation temperature should be over 0°C. If the ambient temperature is lower than 0°C, the cable should be preheated. 

Operating Temperature:

Max permissible continuous operating temperature of conductor shall not exceed 70°C.

Conductor Short-circuit Temperature:

Max temperature at short-circuit shall not exceed 160°C. The short-circuit duration shall not exceed 5 seconds.

Bending Radius:

20(d+D)±5% for single core cable, 15(d+D)±5% for multi-core cable

D = Actual outer diameter of cable (mm), d = Actual diameter of the conductor (mm)

Standard

IEC 12706, IEC 60502 or other standards required by customers.

The requirement for flame retardant property is according to IEC 60332-3 and GB 18380.

Packing

Steel/wooden reel, wooden reel or steel reel.


power cable





XLPE Insulated Power Cable


Application

This product is suitable for transmission and distribution system at the voltage from LV to MV. The power cables can be flame retardant when used as type ZR.

Installation Temperature:

The installation temperature should be over 0°C. If the ambient temperature is lower than 0°C, the cable should be preheated. 

Operating Temperature:

Max permissible continuous operating temperature of conductor shall not exceed 90°C.

Conductor Short-circuit Temperature:

Max temperature at short-circuit shall not exceed 250°C. The short-circuit duration shall not exceed 5 seconds.

Bending Radius:

20(d+D)±5% for single core cable, 15(d+D)±5% for multi-core cable

D = Actual outer diameter of cable (mm), d = Actual diameter of the conductor (mm)

Standard

 IEC 60502, GB 12706, or other standards required by customers.

The requirement for flame retardant property is according to IEC 60332-3 and GB 18380.

Packing

Steel/wooden reel, wooden reel or steel reel.